⚡ EV Charger • 240V / 48A / 100 ft

48 Amp EV Charger Wire Size for 100 Feet Long Run

Quick Answer: Use 4 AWG Copper THHN (Voltage Drop Safe) with a 60 Amp 2-Pole Breaker. For a 100-foot run to a detached garage, upsizing from 6 AWG to 4 AWG copper keeps voltage drop under 1.7% at 48 Amps, ensuring maximum charging speed and zero overheating.

⚠️ Electrical Safety Notice: Always turn off the main service breaker and verify zero voltage with a non-contact tester before working inside any electrical panel.

⚡ Interactive NEC Wire Size & Voltage Drop Calculator

US / Canada AWG Standard
Minimum Wire Size
6 AWG
Copper (75°C NEC)
Breaker / Fuse Size
60 Amp
Includes 125% NEC factor
Voltage Drop
1.29%
PASS (Under 3% NEC limit)
Total Power
11.52 kW
Max Circuit Load

🛒 Complete Installation Materials Checklist

1. Recommended Wire
4 AWG THHN Copper Wire (100 ft)
Check Wire Price →
2. Breaker / Disconnect
60 Amp 2-Pole Breaker + 1 Inch Conduit Fittings
Check Breaker Price →
3. Compatible Equipment
48 Amp Hardwired Smart EV Charger
View on Amazon →

📋 NEC Code & Installation Notes

  • At 100 feet, 6 AWG copper approaches 2.6% voltage drop; stepping up to 4 AWG cuts energy loss by 37%.
  • Use 1-inch PVC or EMT conduit when pulling three 4 AWG THHN conductors.
  • Verify your EV charger terminal lugs accept 4 AWG wire (most Tesla and ChargePoint units accept up to 4 AWG).

Frequently Asked Questions

What wire gauge do I need for 48 amp ev charger wire size for 100 feet long run?
For a 48A load at 240V over 100 feet, the recommended conductor is 4 AWG Copper THHN (Voltage Drop Safe) paired with a 60 Amp 2-Pole Breaker to meet NEC ampacity and keep voltage drop below 3%.
Can I use aluminum wire instead of copper for 48 Amps?
Yes, for feeder runs (such as subpanels or RV pedestals), aluminum THHN/XHHW or SER cable can be used if upsized by 1 to 2 AWG sizes (check the Aluminum option in our calculator above) and terminated with anti-oxidant compound on AL-rated lugs.
Why does distance affect wire size for 48A Hardwired Wall Charger (Long Detached Garage Run)?
Longer wire runs increase electrical resistance, causing voltage drop. Under NEC guidelines, keeping voltage drop under 3% prevents overheating, nuisance breaker trips, and reduced charging or motor efficiency.