50 Amp RV Hookup Wire Size & Breaker for 100 Feet

Quick Answer: Use 4 AWG Copper (or 2 AWG Aluminum URD) with a 50 Amp 2-Pole Breaker. To power a 50 Amp RV pedestal 100 feet from your main panel without A/C compressor brownouts, install 4 AWG copper THWN or 2 AWG aluminum direct-burial wire.

⚠️ Electrical Safety Notice: Always turn off the main service breaker and verify zero voltage with a non-contact tester before working inside any electrical panel.

⚡ Interactive NEC Wire Size & Voltage Drop Calculator

US / Canada AWG Standard
Minimum Wire Size
6 AWG
Copper (75°C NEC)
Breaker / Fuse Size
60 Amp
Includes 125% NEC factor
Voltage Drop
1.29%
PASS (Under 3% NEC limit)
Total Power
11.52 kW
Max Circuit Load

🛒 Complete Installation Materials Checklist

1. Recommended Wire
50 Amp Outdoor RV Power Outlet Box
Check Wire Price →
2. Breaker / Disconnect
50 Amp 2-Pole Standard Circuit Breaker
Check Breaker Price →
3. Compatible Equipment
50 Amp RV Surge Protector with Circuit Analyzer
View on Amazon →

📋 NEC Code & Installation Notes

  • While 6 AWG copper is rated for 55A-65A, a 100-foot run causes nearly 2.7% voltage drop when dual RV air conditioners start.
  • Upsizing to 4 AWG copper or 2 AWG aluminum XHHW/URD keeps voltage drop below 1.7% and saves money on long trench runs.
  • 50A RV pedestals require 4 conductors (Hot 1, Hot 2, Neutral, Ground).

Frequently Asked Questions

What wire gauge do I need for 50 amp rv hookup wire size & breaker for 100 feet?
For a 50A load at 240V over 100 feet, the recommended conductor is 4 AWG Copper (or 2 AWG Aluminum URD) paired with a 50 Amp 2-Pole Breaker to meet NEC ampacity and keep voltage drop below 3%.
Can I use aluminum wire instead of copper for 50 Amps?
Yes, for feeder runs (such as subpanels or RV pedestals), aluminum THHN/XHHW or SER cable can be used if upsized by 1 to 2 AWG sizes (check the Aluminum option in our calculator above) and terminated with anti-oxidant compound on AL-rated lugs.
Why does distance affect wire size for 50A 120/240V RV Power Pedestal (NEMA 14-50R)?
Longer wire runs increase electrical resistance, causing voltage drop. Under NEC guidelines, keeping voltage drop under 3% prevents overheating, nuisance breaker trips, and reduced charging or motor efficiency.